EPG
The mechanical
ventilation control can be specified here. The Ventilation control type in the
top of the screen is determined based on the mechanical ventilation control.
This Ventilation control type is applied in the energy performance calculation
EPG.
•No control
•Time control without zoning
•Time control with two or more zones,
•CO2 control exhaust only
•CO2 control in residential area
•CO2-control with two or more zones,
•CO2 control in residential area with cooker
|
NEN 8088, Tables 2 and 5 |
HL
In buildings with
mechanical supply of ventilation air, the calculations can take it into account
when the ventilation is in night mode when warming up the building. During this
night mode the ventilation performs at 50% power in housing and it is inactive
in non-residential buildings. The power required for (possibly) warming up the
ventilation air has been charged already. This power is not used during heating
of the building (partly for housing), therefore, it can be used to heat up the
building. As a result, the required power for heating of the ventilation (partly
for housing) air is subtracted from the power to be installed in the room. In
heat loss calculations, it is always safer not to work with the ventilation in
night mode when warming up the building.
BS
When conditional night heating is present; the
central air installation is controlled based on the conditions in one of the
rooms. Night heating is activated if the temperature in the room is below
the switching temperature. In this case the air flow is switched to the flow at
conditional night heating. Conditional night heating with ventilation air is
only possible if:
• A Heating/cooling coil is present;
•A flow rate for night mode has been specified in Ventilation;
•The flow rate at conditional night ventilation is greater than the flow rate at (normal) night ventilation.
If conditional night heating is chosen, the heating curve for the night is applied. These heating curves, i.e. night time mode for both Distribution and Supply temperatureError! Not a valid bookmark self-reference., need to be defined.
Standard 16 °C BS
This is the
room temperature at which the air heater and ventilators are activated. Night
heating will be activated when the room temperature is below this specified
temperature. This is also called the activation temperature. This setting
only becomes visible if conditional night heating has been chosen.
Standard 17 °C BS
This is the
room temperature at which the air heater and ventilators are deactivated. Night
heating will not be activated when the room temperature is above this specified
temperature. This is also called the deactivation temperature. This setting only
becomes visible if conditional night heating has been chosen.
BS
In this screen you can
specify whether the night cooling is provided by the intake of additional air
and/or by the central air cooler. The central air handling system is controlled
based on the conditions in one of the rooms for conditional night cooling. The
night cooling is activated when the room temperature of this room is below the
switching temperature and the temperature difference (between inside and
outside) is larger than specified. In this case the flow rate for conditional
night cooling is applied. Conditional night cooling with ventilation air is only
possible if:
• A flow rate for night mode has been specified in the Ventilation template;
• The flow rate at conditional night ventilation is greater than the flow rate at (normal) night ventilation.
Standard 23 °C BS
This is the room temperature at which the air cooler and
ventilators are activated. Night cooling will be activated when the room
temperature is above this specified temperature. This is also called the
activation temperature. This setting only becomes visible if conditional night
cooling has been chosen.
Standard 5 °C BS
This is the outside
temperature at which the air cooler and ventilators are activated. Night cooling
will be activated when the outside temperature is above this specified
temperature. This setting only becomes visible if conditional night cooling has
been chosen.
[K] Standard 5 K BS
Conditional night
cooling may only be activated if the difference between the room temperature and
the outside temperature is greater than a specified minimum value. The room
temperature is considered at the end of the previous hour. This setting only
becomes visible if conditional night cooling has been chosen.
Standard 18 °C BS
This is the
room temperature at which the air cooler and ventilators are deactivated. Night
cooling will not be activated when the room temperature is below this specified
temperature. This is also called the deactivation temperature. This setting only
becomes visible if conditional night heating has been chosen.