Related to: Infiltration.
Values for infiltration qi flow in m³/s per m² outer surface (external partition, including glazing and doors) depending qv, 10, cart and ventilation system for homes/residential buildings that meet the new requirements of the Building.
Ventilation |
qv, 10, cart | ||||
≤ 0.3 |
0.5 |
1.0 |
1.5 |
≥ 2.0 | |
Natural supply and natural exhaust ventilation (system A) |
|
|
17:10 -5 |
26.10 -5 |
39.10 -5 |
Natural supply and central *) mechanical exhaust ventilation (System C) |
|
|
16:10 -5 |
23:10 -5 |
34.10 -5 |
Natural supply and mechanical exhaust ventilation per departure (system C; variant) |
10:10 -5 |
12:10 -5 |
19:10 -5 |
30.10 -5 |
42.10 -5 |
Mechanical supply and natural exhaust ventilation (System B) |
11:10 -5 |
14:10 -5 |
21:10 -5 |
33.10 -5 |
45.10 -5 |
Mechanical supply and mechanical exhaust ventilation (balanced ventilation) (system D) |
10:10 -5 |
12:10 -5 |
19:10 -5 |
|
|
*) Central exhaust ventilation air is discharge from only kitchen, toilet and bathroom |
• ISSO 51 Table 4.2 and 4.3, you must ensure that the tables are based on a usable area of 100 sqm.
• ISSO 53 Table 4.3