This sub screen only applies to rooms which are higher than 5 metres (ISSO 57)
[Factor] HL
In rooms which are higher than 5 metres, the heating
system mainly determines the temperature gradient in the room. The recirculation
rate leads to a reduction in this temperature gradient. The corresponding
reduction factor can be indicated here; it should be determined based on ISSO
57, Table 2.3 and Figure 2.2.
•Smaller or equal to singular gives a reduction factor of 1.00;
•2-fold gives a reduction factor of 0.75;
•4-fold gives a reduction factor of 0.55;
•6-fold gives a reduction factor of 0.40;
•8-fold gives a reduction factor of 0.30;
•10-fold gives a reduction factor of 0.20;
•User defined: the reduction factor is specified by the user.
HL |
ISSO Publication 57 (2011), Table 2.3 and Figure 2.2 Maximum circulation rate depending on the contents of the space |