BS
This schedule is linked to emissive devices and air handling units. It is defined based on three distinct values: daytime operations, night-time operations/standby, and off. Daytime operations are shaded in green, night-time operations are shaded in yellow, and off remains white. Settings associated with the night-time operations include e.g. the design temperatures, the heating allowance (see room requirements), and the ventilation (see the ventilation-template). Please select the required period of time as described above, and click on the desired value.
Recommended values are:
• Inside houses: from 06:00 to 23:00, i.e. time slots 7-23. The central heating system is switched off during night and it is activated one hour before the time of use;
• Inside offices: from 05:00 to 18:00, i.e. time slots 6-18;
• Inside schools with daytime classes: from 05:00 to 16:00, i.e. time slots 6-16;
• Inside schools with daytime and night-time classes: from 05:00 to 22:00, i.e. time slots 6-22.
BS |
ISSO Publicatie 32 (2011), paragraaf 1.7 Bedrijfstijd
|