HL BS EPG
This box
indicates whether a mechanical exhaust for the air handling system is present.
Checking this box affects the ventilation system type in the top of the Air
handling screen.
HL
Checking this box
indicates that a variant on ventilation system C should be used in the heat loss
calculations for housing. In this variant the air is extracted for each room
separately (demand-controlled ventilation), rather than being extracted
centrally in the kitchen, bath room, and toilet. As a result the heat loss
calculations are performed with a façade which is more airtight; a lower
qv,10 value can be specified.
[Pieces] EPG
This number represents the number of ventilators
within the air handling unit. This input can only be specified in case the
Ventilation power is determined detailed for the energy performance in the EPG,
as should be indicated in the Project settings.
EPG
This is the nominal
power per fan in W. In case multiple fans have been defined, the nominal power
is multiplied by the number of fans.
HL BS EPG
This indicates
whether the heating of air caused by the exhaust fan should be taken into
account. The amount of heating should be specified in Kelvin.
•Vabi default the heating by the exhaust fan is taken as 1.5 K
•User defined the heating by the exhaust fan can be specified between 0 and 4 K