EPG
With this box it can
be specified whether the heat emission is controlled separately. The control can
be by means of a room thermostat, a thermostat valve, etc. If no control is
applied the emission efficiency is multiplied by 0.8. The control is only
applied for heating in housing.
|
NEN 7120, Table 14.1 |
EPG
With this box it can
be specified whether individual metering is applied. If no metering is applied,
the emission efficiency is reduced by 0.10. Metering is only applied in housing
with collective heating.
|
NEN 7120, Table 14.1 |
BS
The system can be
controlled based on air- or comfort temperature, or by an ATG class. This
control applies to the complete installation concept defined in Emissive devices.
•Air temperature is the average air temperature in the room
•Comfort temperature is the average comfort temperature in the room. Tcomfort = average of (Tair; Tradiation). If the comfort temperature differs from the air temperature, the room has either hot or cold surfaces.
•ATG class A for alpha building
•ATG class B for alpha building
•ATG class C for alpha building
•ATG class A for beta building
•ATG class B for beta building
•ATG class C for beta building
[Selection] BS
A Schedule of HVAC, in which the periods of
daytime- and night-time operation of the complete installation concept have been
defined, is selected here.