Control

Individual control

 EPG
With this box it can be specified whether the heat emission is controlled separately. The control can be by means of a room thermostat, a thermostat valve, etc. If no control is applied the emission efficiency is multiplied by 0.8. The control is only applied for heating in housing.

nen-logo_voor_internet.jpg

NEN 7120, Table 14.1

NEN Normshop

Individual metering

 EPG
With this box it can be specified whether individual metering is applied. If no metering is applied, the emission efficiency is reduced by 0.10. Metering is only applied in housing with collective heating.

nen-logo_voor_internet.jpg

NEN 7120, Table 14.1

NEN Normshop

Control on

 BS
The system can be controlled based on air- or comfort temperature, or by an ATG class.  This control applies to the complete installation concept defined in Emissive devices.

      Air temperature is the average air temperature in the room

      Comfort temperature is the average comfort temperature in the room. Tcomfort = average of (Tair; Tradiation). If the comfort temperature differs from the air temperature, the room has either hot or cold surfaces.

      ATG class A for alpha building

      ATG class B for alpha building

      ATG class C for alpha building

      ATG class A for beta building

      ATG class B for beta building

      ATG class C for beta building

Operational hours

[Selection] BS
A Schedule of HVAC, in which the periods of daytime- and night-time operation of the complete installation concept have been defined, is selected here.